['Air Programs']
['Air Quality']
08/31/2024
...
§60.700 Applicability and designation of affected facility.
(a) The provisions of this subpart apply to each affected facility designated in paragraph (b) of this section that is part of a process unit that produces any of the chemicals listed in §60.707 as a product, co-product, by-product, or intermediate, except as provided in paragraph (c) of this section.
(b) The affected facility is any of the following for which construction, modification, or reconstruction commenced after June 29, 1990, and on or before April 25, 2023:
(1) Each reactor process not discharging its vent stream into a recovery system.
(2) Each combination of a reactor process and the recovery system into which its vent stream is discharged.
(3) Each combination of two or more reactor processes and the common recovery system into which their vent streams are discharged.
(c) Exemptions from the provisions of paragraph (a) of this section are as follows:
(1) Any reactor process that is designed and operated as a batch operation is not an affected facility.
(2) Each affected facility that has a total resource effectiveness (TRE) index value greater than 8.0 is exempt from all provisions of this subpart except for §§60.702(c); 60.704 (d), (e), and (f); and 60.705 (g), (l)(1), (l)(6), and (t).
(3) Each affected facility in a process unit with a total design capacity for all chemicals produced within that unit of less than 1 gigagram per year (1,100 tons per year) is exempt from all provisions of this subpart except for the recordkeeping and reporting requirements in §60.705 (i), (l)(5), and (n).
(4) Each affected facility operated with a vent stream flow rate less than 0.011 scm/min is exempt from all provisions of this subpart except for the test method and procedure and the recordkeeping and reporting requirements in §§60.704(g) and 70.705(h), (l)(4), and (o).
(5) If the vent stream from an affected facility is routed to a distillation unit subject to subpart NNN of this part or subpart NNNa of this part, and has no other releases to the air except for a pressure relief valve, the facility is exempt from all provisions of this subpart except for §60.705(r).
(6) Any reactor process operating as part of a process unit which produces beverage alcohols, or which uses, contains, and produces no VOC is not an affected facility.
(7) Any reactor process that is subject to the provisions of subpart DDD is not an affected facility.
(8) Each affected facility operated with a concentration of total organic compounds (TOC) (less methane and ethane) in the vent stream less than 300 ppmv as measured by Method 18 of appendix A-6 to this part or ASTM D6420-18 (incorporated by reference, see §60.17) as specified in §60.704(b)(4), or a concentration of TOC in the vent stream less than 150 ppmv as measured by Method 25A of appendix A-7 to this part is exempt from all provisions of this subpart except for the test method and procedure and the reporting and recordkeeping requirements in §§60.704(h) and 60.705(j), (l)(8), and (p).
(d) Alternative means of compliance - (1) Option to comply with part 65. Owners or operators of process vents that are subject to this subpart may choose to comply with the provisions of 40 CFR part 65, subpart D, to satisfy the requirements of §§60.702 through 60.705 and 60.708. The provisions of 40 CFR part 65 also satisfy the criteria of paragraphs (c)(2), (4), and (8) of this section. Other provisions applying to an owner or operator who chooses to comply with 40 CFR part 65 are provided in 40 CFR 65.1.
(2) Part 60, subpart A. Owners or operators who choose to comply with 40 CFR part 65, subpart D, must also comply with §§60.1, 60.2, 60.5, 60.6, 60.7(a)(1) and (4), 60.14, 60.15, and 60.16 for those process vents. All sections and paragraphs of subpart A of this part that are not mentioned in this paragraph (d)(2) do not apply to owners or operators of process vents complying with 40 CFR part 65, subpart D, except that provisions required to be met prior to implementing 40 CFR part 65 still apply. Owners and operators who choose to comply with 40 CFR part 65, subpart D, must comply with 40 CFR part 65, subpart A.
(3) Compliance date. Owners or operators who choose to comply with 40 CFR part 65, subpart D at initial startup shall comply with paragraphs (d)(1) and (2) of this section for each vent stream on and after the date on which the initial performance test is completed, but not later than 60 days after achieving the maximum production rate at which the affected facility will be operated, or 180 days after the initial startup, whichever date comes first.
(4) Initial startup notification. Each owner or operator subject to the provisions of this subpart that chooses to comply with 40 CFR part 65, subpart D, at initial startup shall notify the Administrator of the specific provisions of 40 CFR 65.63(a)(1), (2), or (3), with which the owner or operator has elected to comply. Notification shall be submitted with the notifications of initial startup required by 40 CFR 65.5(b).
(e) Owners and operators of flares that are subject to the flare related requirements of this subpart and flare related requirements of any other regulation in this part or 40 CFR part 61 or 63, may elect to comply with the requirements in §60.709a in lieu of all flare related requirements in any other regulation in this part or 40 CFR part 61 or 63.
(Note:
The intent of these standards is to minimize emissions of VOC through the application of best demonstrated technology (BDT). The numerical emission limits in these standards are expressed in terms of TOC, measured as TOC less methane and ethane. This emission limit reflects the performance of BDT.)
[58 FR 45962, Aug. 31, 1993, as amended at 60 FR 58238, Nov. 27, 1995; 65 FR 78279, Dec. 14, 2000; 89 FR 43067, May 16, 2024]
§60.701 Definitions.
As used in this subpart, all terms not defined here shall have the meaning given them in the Act and in subpart A of part 60, and the following terms shall have the specific meanings given them.
Batch operation means any noncontinuous reactor process that is not characterized by steady-state conditions and in which reactants are not added and products are not removed simultaneously.
Boiler means any enclosed combustion device that extracts useful energy in the form of steam and is not an incinerator.
By compound means by individual stream components, not carbon equivalents.
Car-seal means a seal that is placed on a device that is used to change the position of a valve (e.g., from opened to closed) in such a way that the position of the valve cannot be changed without breaking the seal.
Combustion device means an individual unit of equipment, such as an incinerator, flare, boiler, or process heater, used for combustion of a vent stream discharged from the process vent.
Continuous recorder means a data recording device recording an instantaneous data value at least once every 15 minutes.
Flame zone means the portion of the combustion chamber in a boiler or process heater occupied by the flame envelope.
Flow indicator means a device which indicates whether gas flow is present in a line.
Halogenated vent stream means any vent stream determined to have a total concentration (by volume) of compounds containing halogens of 20 ppmv (by compound) or greater.
Incinerator means an enclosed combustion device that is used for destroying organic compounds. If there is energy recovery, the energy recovery section and the combustion chambers are not of integral design. That is, the energy recovery section and the combustion section are not physically formed into one manufactured or assembled unit but are joined by ducts or connections carrying flue gas.
Primary fuel means the fuel fired through a burner or a number of similar burners. The primary fuel provides the principal heat input to the device, and the amount of fuel is sufficient to sustain operation without the addition of other fuels.
Process heater means a device that transfers heat liberated by burning fuel directly to process streams or to heat transfer liquids other than water.
Process unit means equipment assembled and connected by pipes or ducts to produce, as intermediates or final products, one or more of the chemicals in §60.707. A process unit can operate independently if supplied with sufficient feed or raw materials and sufficient product storage facilities.
Product means any compound or chemical listed in §60.707 which is produced for sale as a final product as that chemical, or for use in the production of other chemicals or compounds. By-products, co-products, and intermediates are considered to be products.
Reactor processes are unit operations in which one or more chemicals, or reactants other than air, are combined or decomposed in such a way that their molecular structures are altered and one or more new organic compounds are formed.
Recovery device means an individual unit of equipment, such as an absorber, carbon adsorber, or condenser, capable of and used for the purpose of recovering chemicals for use, reuse, or sale.
Recovery system means an individual recovery device or series of such devices applied to the same vent stream.
Relief valve means a valve used only to release an unplanned, nonroutine discharge. A relief valve discharge results from an operator error, a malfunction such as a power failure or equipment failure, or other unexpected cause that requires immediate venting of gas from process equipment in order to avoid safety hazards or equipment damage.
Secondary fuel means a fuel fired through a burner other than a primary fuel burner. The secondary fuel may provide supplementary heat in addition to the heat provided by the primary fuel.
Total organic compounds or TOC means those compounds measured according to the procedures in §60.704(b)(4). For the purposes of measuring molar composition as required in §60.704(d)(2)(i) and §60.704(d)(2)(ii), hourly emission rate as required in §60.704(d)(5) and §60.704(e), and TOC concentration as required in §60.705(b)(4) and §60.705(f)(4), those compounds which the Administrator has determined do not contribute appreciably to the formation of ozone are to be excluded.
Total resource effectiveness or TRE index value means a measure of the supplemental total resource requirement per unit reduction of TOC associated with a vent stream from an affected reactor process facility, based on vent stream flow rate, emission rate of TOC, net heating value, and corrosion properties (whether or not the vent stream contains halogenated compounds), as quantified by the equation given under §60.704(e).
Vent stream means any gas stream discharged directly from a reactor process to the atmosphere or indirectly to the atmosphere after diversion through other process equipment. The vent stream excludes relief valve discharges and equipment leaks.
[89 FR 43067, May 16, 2024]
§60.702 Standards.
Each owner or operator of any affected facility shall comply with paragraph (a), (b), or (c) of this section for each vent stream on and after the date on which the initial performance test required by §§60.8 and 60.704 is completed, but not later than 60 days after achieving the maximum production rate at which the affected facility will be operated, or 180 days after the initial start-up, whichever date comes first. Each owner or operator shall either:
(a) Reduce emissions of TOC (less methane and ethane) by 98 weight-percent, or to a TOC (less methane and ethane) concentration of 20 ppmv, on a dry basis corrected to 3 percent oxygen, whichever is less stringent. If a boiler or process heater is used to comply with this paragraph, then the vent stream shall be introduced into the flame zone of the boiler or process heater; or
(b) Combust the emissions in a flare that meets the requirements of §60.18; or
(c) Maintain a TRE index value greater than 1.0 without use of a VOC emission control device.
§60.703 Monitoring of emissions and operations.
(a) The owner or operator of an affected facility that uses an incinerator to seek to comply with the TOC emission limit specified under §60.702(a) shall install, calibrate, maintain, and operate according to manufacturer's specifications the following equipment:
(1) A temperature monitoring device equipped with a continuous recorder and having an accuracy of ±1 percent of the temperature being monitored expressed in degrees Celsius or ±0.5°C, whichever is greater.
(i) Where an incinerator other than a catalytic incinerator is used, a temperature monitoring device shall be installed in the firebox or in the ductwork immediately downstream of the firebox in a position before any substantial heat exchange is encountered.
(ii) Where a catalytic incinerator is used, temperature monitoring devices shall be installed in the gas stream immediately before and after the catalyst bed.
(2) A flow indicator that provides a record of vent stream flow diverted from being routed to the incinerator at least once every 15 minutes for each affected facility, except as provided in paragraph (a)(2)(ii) of this section.
(i) The flow indicator shall be installed at the entrance to any bypass line that could divert the vent stream from being routed to the incinerator, resulting in its emission to the atmosphere.
(ii) Where the bypass line valve is secured in the closed position with a car-seal or a lock-and-key type configuration, a flow indicator is not required. A visual inspection of the seal or closure mechanism shall be performed at least once every month to ensure that the valve is maintained in the closed position and the vent stream is not diverted through the bypass line.
(b) The owner or operator of an affected facility that uses a flare to seek to comply with §60.702(b) shall install, calibrate, maintain, and operate according to manufacturer's specifications the following equipment:
(1) A heat sensing device, such as an ultraviolet beam sensor or thermocouple, at the pilot light to indicate the continuous presence of a flame.
(2) A flow indicator that provides a record of vent stream flow diverted from being routed to the flare at least once every 15 minutes for each affected facility, except as provided in paragraph (b)(2)(ii) of this section.
(i) The flow indicator shall be installed at the entrance to any bypass line that could divert the vent stream from being routed to the flare, resulting in its emission to the atmosphere.
(ii) Where the bypass line valve is secured in the closed position with a car-seal or a lock-and-key type configuration, a flow indicator is not required. A visual inspection of the seal or closure mechanism shall be performed at least once every month to ensure that the valve is maintained in the closed position and the vent stream is not diverted through the bypass line.
(c) The owner or operator of an affected facility that uses a boiler or process heater to seek to comply with §60.702(a) shall install, calibrate, maintain and operate according to the manufacturer's specifications the following equipment:
(1) A flow indicator that provides a record of vent stream flow diverted from being routed to the boiler or process heater at least once every 15 minutes for each affected facility, except as provided in paragraph (c)(1)(ii) of this section.
(i) The flow indicator shall be installed at the entrance to any bypass line that could divert the vent stream from being routed to the boiler or process heater, resulting in its emission to the atmosphere.
(ii) Where the bypass line valve is secured in the closed position with a car-seal or a lock-and-key type configuration, a flow indicator is not required. A visual inspection of the seal or closure mechanism shall be performed at least once every month to ensure that the valve is maintained in the closed position and the vent stream is not diverted through the bypass line.
(2) A temperature monitoring device in the firebox equipped with a continuous recorder and having an accuracy of ±1 percent of the temperature being monitored expressed in degrees Celsius or ±0.5°C, whichever is greater, for boilers or process heaters of less than 44 MW (150 million Btu/hr) design heat input capacity. Any vent stream introduced with primary fuel into a boiler or process heater is exempt from this requirement.
(d) The owner or operator of an affected facility that seeks to demonstrate compliance with the TRE index value limit specified under §60.702(c) shall install, calibrate, maintain, and operate according to manufacturer's specifications the following equipment, unless alternative monitoring procedures or requirements are approved for that facility by the Administrator:
(1) Where an absorber is the final recovery device in the recovery system:
(i) A scrubbing liquid temperature monitoring device having an accuracy of ±1 percent of the temperature being monitored expressed in degrees Celsius or ±0.5°C, whichever is greater, and a specific gravity monitoring device having an accuracy of ±0.02 specific gravity units, each equipped with a continuous recorder; or
(ii) An organic monitoring device used to indicate the concentration level of organic compounds exiting the recovery device based on a detection principle such as infra-red, photoionization, or thermal conductivity, each equipped with a continuous recorder.
(2) Where a condenser is the final recovery device in the recovery system:
(i) A condenser exit (product side) temperature monitoring device equipped with a continuous recorder and having an accuracy of ±1 percent of the temperature being monitored expressed in degrees Celsius or ±0.5°C, whichever is greater; or
(ii) An organic monitoring device used to indicate the concentration level of organic compounds exiting the recovery device based on a detection principle such as infra-red, photoionization, or thermal conductivity, each equipped with a continuous recorder.
(3) Where a carbon adsorber is the final recovery device unit in the recovery system:
(i) An integrating steam flow monitoring device having an accuracy of ±10 percent, and a carbon bed temperature monitoring device having an accuracy of ±1 percent of the temperature being monitored expressed in degrees Celsius or ±0.5°C, whichever is greater, both equipped with a continuous recorder; or
(ii) An organic monitoring device used to indicate the concentration level of organic compounds exiting the recovery device based on a detection principle such as infra-red, photoionization, or thermal conductivity, each equipped with a continuous recorder.
(e) An owner or operator of an affected facility seeking to demonstrate compliance with the standards specified under §60.702 with a control device other than an incinerator, boiler, process heater, or flare; or a recovery device other than an absorber, condenser, or carbon adsorber, shall provide to the Administrator information describing the operation of the control device or recovery device and the process parameter(s) which would indicate proper operation and maintenance of the device. The Administrator may request further information and will specify appropriate monitoring procedures or requirements.
§60.704 Test methods and procedures.
(a) For the purpose of demonstrating compliance with §60.702, all affected facilities shall be run at full operating conditions and flow rates during any performance test.
(b) The following methods in appendix A to this part, except as provided under §60.8(b), shall be used as reference methods to determine compliance with the emission limit or percent reduction efficiency specified under §60.702(a).
(1) Method 1 or 1A, as appropriate, for selection of the sampling sites. The control device inlet sampling site for determination of vent stream molar composition or TOC (less methane and ethane) reduction efficiency shall be prior to the inlet of the control device and after the recovery system.
(2) Method 2, 2A, 2C, or 2D, as appropriate, for determination of the gas volumetric flow rates.
(3) The emission rate correction factor, integrated sampling and analysis procedures of Method 3B of appendix A-2 to this part, or the manual method in ANSI/ASME PTC 19.10-1981 incorporated by reference, see §60.17), shall be used to determine the oxygen concentration (%O2d) for the purposes of determining compliance with the 20 ppmv limit. The sampling site shall be the same as that of the TOC samples, and the samples shall be taken during the same time that the TOC samples are taken. The TOC concentration corrected to 3 percent O2 (Cc) shall be computed using the following equation:
Where:
C c = Concentration of TOC corrected to 3 percent O 2 , dry basis, ppm by volume.
C TOC = Concentration of TOC (minus methane and ethane), dry basis, ppm by volume.
%O 2d = Concentration of O 2 , dry basis, percent by volume.
(4) Method 18 of appendix A-6 to this part to determine the concentration of TOC in the control device outlet and the concentration of TOC in the inlet when the reduction efficiency of the control device is to be determined. ASTM D6420-18 (incorporated by reference, see §60.17) may be used in lieu of Method 18 of appendix A-6 to this part, if the target compounds are all known and are all listed in Section 1.1 of ASTM D6420-18 as measurable; ASTM D6420-18 may not be used for methane and ethane; and ASTM D6420-18 may not be used as a total VOC method.
(i) The minimum sampling time for each run shall be 1 hour in which either an integrated sample or four grab samples shall be taken. If grab sampling is used, then the samples shall be taken at approximately 15-minute intervals.
(ii) The emission reduction (R) of TOC (minus methane and ethane) shall be determined using the following equation:
where:
R = Emission reduction, percent by weight.
Ei = Mass rate of TOC entering the control device, kg TOC/hr.
Eo = Mass rate of TOC discharged to the atmosphere, kg TOC/hr.
(iii) The mass rates of TOC (Ei, Eo) shall be computed using the following equations:
where:
Cij, Coj = Concentration of sample component “j” of the gas stream at the inlet and outlet of the control device, respectively, dry basis, ppm by volume.
Mij, Moj = Molecular weight of sample component “j” of the gas stream at the inlet and outlet of the control device, respectively, g/g-mole (lb/lb-mole).
Qi, Qo = Flow rate of gas stream at the inlet and outlet of the control device, respectively, dscm/min (dscf/hr).
K2 = Constant, 2.494 × 10−6 (l/ppm) (g-mole/scm) (kg/g) (min/hr), where standard temperature for (g-mole/scm) is 20°C.
(iv) The TOC concentration (CTOC) is the sum of the individual components and shall be computed for each run using the following equation:
where:
CTOC = Concentration of TOC (minus methane and ethane), dry basis, ppm by volume.
Cj = Concentration of sample components “j”, dry basis, ppm by volume.
n = Number of components in the sample.
(5) The requirement for an initial performance test is waived, in accordance with §60.8(b), for the following:
(i) When a boiler or process heater with a design heat input capacity of 44 MW (150 million Btu/hour) or greater is used to seek compliance with §60.702(a).
(ii) When a vent stream is introduced into a boiler or process heater with the primary fuel.
(iii) The Administrator reserves the option to require testing at such other times as may be required, as provided for in section 114 of the Act.
(6) For purposes of complying with the 98 weight-percent reduction in §60.702(a), if the vent stream entering a boiler or process heater with a design capacity less than 44 MW (150 million Btu/hour) is introduced with the combustion air or as secondary fuel, the weight-percent reduction of TOC (minus methane and ethane) across the combustion device shall be determined by comparing the TOC (minus methane and ethane) in all combusted vent streams, primary fuels, and secondary fuels with the TOC (minus methane and ethane) exiting the combustion device.
(c) When a flare is used to seek to comply with §60.702(b), the flare shall comply with the requirements of §60.18.
(d) The following test methods, except as provided under §60.8(b), shall be used for determining the net heating value of the gas combusted to determine compliance under §60.702(b) and for determining the process vent stream TRE index value to determine compliance under §§60.700(c)(2) and 60.702(c).
(1)(i) Method 1 or 1A of appendix A-1 to this part, as appropriate, for selection of the sampling site. The sampling site for the vent stream flow rate and molar composition determination prescribed in §60.704(d)(2) and (3) shall be, except for the situations outlined in paragraph (d)(1)(ii) of this section, prior to the inlet of any control device, prior to any postreactor dilution of the stream with air, and prior to any postreactor introduction of halogenated compounds into the process vent stream. No traverse site selection method is needed for vents smaller than 4 inches in diameter.
(ii) If any gas stream other than the reactor vent stream is normally conducted through the final recovery device:
(A) The sampling site for vent stream flow rate and molar composition shall be prior to the final recovery device and prior to the point at which any nonreactor stream or stream from a nonaffected reactor process is introduced.
(B) The efficiency of the final recovery device is determined by measuring the TOC concentration using Method 18 of appendix A-6 to this part, or ASTM D6420-18 (incorporated by reference, see §60.17) as specified in paragraph (b)(4) of this section, at the inlet to the final recovery device after the introduction of any vent stream and at the outlet of the final recovery device.
(C) This efficiency of the final recovery device shall be applied to the TOC concentration measured prior to the final recovery device and prior to the introduction of any nonreactor stream or stream from a nonaffected reactor process to determine the concentration of TOC in the reactor process vent stream from the final recovery device. This concentration of TOC is then used to perform the calculations outlined in paragraphs (d)(4) and (5) of this section.
(2) The molar composition of the process vent stream shall be determined as follows:
(i) Method 18 of appendix A-6 to this part, or ASTM D6420-18 (incorporated by reference, see §60.17) as specified in paragraph (b)(4) of this section, to measure the concentration of TOC including those containing halogens.
(ii) ASTM D1946-77 or 90 (Reapproved 1994) (incorporation by reference as specified in §60.17 of this part) to measure the concentration of carbon monoxide and hydrogen.
(iii) Method 4 of appendix A-3 to this part to measure the content of water vapor.
(3) The volumetric flow rate shall be determined using Method 2, 2A, 2C, or 2D of appendix A-1 to this part, as appropriate.
(4) The net heating value of the vent stream shall be calculated using the following equation:
Where:
H T = Net heating value of the sample, MJ/scm, where the net enthalpy per mole of vent stream is based on combustion at 25 °C and 760 mm Hg, but the standard temperature for determining the volume corresponding to one mole is 20 °C, as in the definition of Q s (vent stream flow rate).
K 1 = Constant, 1.740 × 10 −7 (l/ppm) (g-mole/scm) (MJ/kcal), where standard temperature for (g-mole/scm) is 20 °C.
C j = Concentration on a dry basis of compound j in ppm, as measured for organics by Method 18 of appendix A-6 to this part, or ASTM D6420-18 (incorporated by reference, see §60.17) as specified in paragraph (b)(4) of this section, and measured for hydrogen and carbon monoxide by ASTM D1946-77 or 90 (Reapproved 1994) (incorporated by reference, see §60.17) as indicated in paragraph (d)(2) of this section.
H j = Net heat of combustion of compound j, kcal/g-mole, based on combustion at 25 °C and 760 mm Hg. The heats of combustion of vent stream components would be required to be determined using ASTM D2382-76 or 88 or D4809-95 (incorporated by reference, see §60.17) if published values are not available or cannot be calculated.
B ws = Water vapor content of the vent stream, proportion by volume.
(5) The emission rate of TOC in the vent stream shall be calculated using the following equation:
Where:
E TOC = Emission rate of TOC in the sample, kg/hr.
K 2 = Constant, 2.494 × 10 −6 (l/ppm) (g-mole/scm) (kg/g) (min/hr), where standard temperature for (g-mole/scm) is 20 °C.
C j = Concentration on a dry basis of compound j in ppm as measured by Method 18 of appendix A-6 to this part, or ASTM D6420-18 (incorporated by reference, see §60.17) as specified in paragraph (b)(4) of this section, as indicated in paragraph (d)(2) of this section.
M j = Molecular weight of sample j, g/g-mole.
Q s = Vent stream flow rate (dscm/min) at a temperature of 20 °C.
(6) The total vent stream concentration (by volume) of compounds containing halogens (ppmv, by compound) shall be summed from the individual concentrations of compounds containing halogens which were measured by Method 18 of appendix A-6 to this part, or ASTM D6420-18 (incorporated by reference, see §60.17) as specified in paragraph (b)(4) of this section.
(e) For purposes of complying with §§60.700(c)(2) and 60.702(c), the owner or operator of a facility affected by this subpart shall calculate the TRE index value of the vent stream using the equation for incineration in paragraph (e)(1) of this section for halogenated vent streams. The owner or operator of an affected facility with a nonhalogenated vent stream shall determine the TRE index value by calculating values using both the incinerator equation in (e)(1) of this section and the flare equation in (e)(2) of this section and selecting the lower of the two values.
(1) The equation for calculating the TRE index value of a vent stream controlled by an incinerator is as follows:
(i) Where for a vent stream flow rate (scm/min) at a standard temperature of 20°C that is greater than or equal to 14.2 scm/min:
TRE = TRE index value.
Qs = Vent stream flow rate (scm/min) at a standard temperature of 20°C.
HT = Vent stream net heating value (MJ/scm), where the net enthalpy per mole of vent stream is based on combustion at 25°C and 760 mm Hg, but the standard temperature for determining the volume corresponding to one mole is 20°C as in the definition of Qs.
Ys = Qs for all vent stream categories listed in table 1 except for Category E vent streams where Ys = (Qs)(HT)/3.6.
ETOC = Hourly emissions of TOC reported in kg/hr.
a, b, c, d, e, and f are coefficients. The set of coefficients that apply to a vent stream can be obtained from table 1.
a | b | c | d | e | f | |
---|---|---|---|---|---|---|
DESIGN CATEGORY A1. FOR HALOGENATED PROCESS VENT STREAMS, IF 0≤NET HEATING VALUE (MJ/scm)≤3.5: Qs = Vent Stream Flow Rate (scm/min) | ||||||
14.2≤Qs≤18.8 | 19.18370 | 0.27580 | 0.75762 | −0.13064 | 0 | 0.01025 |
18.8<Qs≤699 | 20.00563 | 0.27580 | 0.30387 | −0.13064 | 0 | 0.01025 |
699<Qs≤1,400 | 39.87022 | 0.29973 | 0.30387 | −0.13064 | 0 | 0.01449 |
1,400<Qs≤2,100 | 59.73481 | 0.31467 | 0.30387 | −0.13064 | 0 | 0.01775 |
2,100<Qs≤2,800 | 79.59941 | 0.32572 | 0.30387 | −0.13064 | 0 | 0.02049 |
2,800<Qs≤3,500 | 99.46400 | 0.33456 | 0.30387 | −0.13064 | 0 | 0.02291 |
DESIGN CATEGORY A2. FOR HALOGENATED PROCESS VENT STREAMS, IF NET HEATING VALUE (MJ/scm)>3.5: Qs = Vent Stream Flow Rate (scm/min) | ||||||
14.2<Qs≤18.8 | 18.84466 | 0.26742 | −0.20044 | 0 | 0 | 0.01025 |
18.8<Qs≤699 | 19.66658 | 0.26742 | −0.25332 | 0 | 0 | 0.01025 |
699<Qs≤1,400 | 39.19213 | 0.29062 | −0.25332 | 0 | 0 | 0.01449 |
1,400<Qs≤2,100 | 58.71768 | 0.30511 | −0.25332 | 0 | 0 | 0.01775 |
2,100<Qs≤2,800 | 78.24323 | 0.31582 | −0 25332 | 0 | 0 | 0.02049 |
2,800<Qs≤3,500 | 97.76879 | 0.32439 | −0.25332 | 0 | 0 | 0.02291 |
DESIGN CATEGORY B. FOR NONHALOGENATED PROCESS VENT STREAMS, IF 0≤NET HEATING VALUE (MJ/scm)≤0.48: Qs = Vent Stream Flow Rate (scm/min) | ||||||
14.2≤Qs≤1,340 | 8.54245 | 0.10555 | 0.09030 | −0.17109 | 0 | 0.01025 |
1,340<Qs≤2,690 | 16.94386 | 0.11470 | 0.09030 | −0.17109 | 0 | 0.01449 |
2,690<Qs≤4,040 | 25.34528 | 0.12042 | 0.09030 | −0.17109 | 0 | 0.01775 |
DESIGN CATEGORY C. FOR NONHALOGENATED PROCESS VENT STREAMS, IF 0.48<NET HEATING VALUE (MJ/scm)≤1.9: Qs = Vent Stream Flow Rate (scm/min) | ||||||
14.2≤Qs≤1,340 | 9.25233 | 0.06105 | 0.31937 | −0.16181 | 0 | 0.01025 |
1,340<Qs≤2,690 | 18.36363 | 0.06635 | 0.31937 | −0.16181 | 0 | 0.01449 |
2,690<Qs≤4,040 | 27.47492 | 0.06965 | 0.31937 | −0.16181 | 0 | 0.01775 |
DESIGN CATEGORY D. FOR NONHALOGENATED PROCESS VENT STREAMS, IF 1.9<NET HEATING VALUE (MJ/scm)≤3.6: Qs = Vent Stream Flow Rate (scm/min) | ||||||
14.2≤Qs≤1,180 | 6.67868 | 0.06943 | 0.02582 | 0 | 0 | 0.01025 |
1,180<Qs≤2,370 | 13.21633 | 0.07546 | 0.02582 | 0 | 0 | 0.01449 |
2,370<Qs≤3,550 | 19.75398 | 0.07922 | 0.02582 | 0 | 0 | 0.01755 |
DESIGN CATEGORY E. FOR NONHALOGENATED PROCESS VENT STREAMS, IF NET HEATING VALUE (MJ/scm)>3.6: Ys = Dilution Flow Rate (scm/min) = (Qs) (HT)/3.6 | ||||||
14.2≤Ys≤1,180 | 6.67868 | 0 | 0 | −0.00707 | 0.02220 | 0.01025 |
1,180<Ys≤2,370 | 13.21633 | 0 | 0 | −0.00707 | 0.02412 | 0.01449 |
2,370<Ys≤3,550 | 19.75398 | 0 | 0 | −0.00707 | 0.02533 | 0.01755 |
(ii) For a vent stream flow rate (scm/min) at a standard temperature of 20°C that is less than 14.2 scm/min:
TRE = TRE index value.
Qs = 14.2 scm/min.
HT = (FLOW)(HVAL)/14.2
where the following inputs are used:
FLOW = Vent stream flow rate (scm/min), at a standard temperature of 20°C.
HVAL = Vent stream net heating value (MJ/scm), where the net enthalpy per mole of vent stream is based on combustion at 25°C and 760 mm Hg, but the standard temperature for determining the volume corresponding to one mole is 20°C as in definition of Qs.
Ys = 14.2 scm/min for all vent streams except for Category E vent streams, where Ys = (14.2)(HT)/3.6.
ETOC = Hourly emissions of TOC reported in kg/hr.
a, b, c, d, e, and f are coefficients. The set of coefficients that apply to a vent stream can be obtained from table 1.
(2) The equation for calculating the TRE index value of a vent stream controlled by a flare is as follows:
where:
TRE = TRE index value.
ETOC = Hourly emission rate of TOC reported in kg/hr.
Qs = Vent stream flow rate (scm/min) at a standard temperature of 20°C.
HT = Vent stream net heating value (MJ/scm) where the net enthalpy per mole of offgas is based on combustion at 25°C and 760 mm Hg, but the standard temperature for determining the volume corresponding to one mole is 20°C as in the definition of Qs.
a, b, c, d, and e are coefficients. The set of coefficients that apply to a vent stream can be obtained from table 2.
a | b | c | d | e | |
---|---|---|---|---|---|
HT<11.2 MJ/scm | 2.25 | 0.288 | −0.193 | −0.0051 | 2.08 |
HT≥11.2 MJ/scm | 0.309 | 0.0619 | −0.0043 | −0.0034 | 2.08 |
(f) Each owner or operator of an affected facility seeking to comply with §60.700(c)(2) or §60.702(c) shall recalculate the TRE index value for that affected facility whenever process changes are made. Examples of process changes include changes in production capacity, feedstock type, or catalyst type, or whenever there is replacement, removal, or addition of recovery equipment. The TRE index value shall be recalculated based on test data, or on best engineering estimates of the effects of the change on the recovery system.
(1) Where the recalculated TRE index value is less than or equal to 1.0, the owner or operator shall notify the Administrator within 1 week of the recalculation and shall conduct a performance test according to the methods and procedures required by §60.704 in order to determine compliance with §60.702 (a) or (b). Performance tests must be conducted as soon as possible after the process change but no later than 180 days from the time of the process change.
(2) Where the recalculated TRE index value is less than or equal to 8.0 but greater than 1.0, the owner or operator shall conduct a performance test in accordance with §§60.8 and 60.704 and shall comply with §§60.703, 60.704 and 60.705. Performance tests must be conducted as soon as possible after the process change but no later than 180 days from the time of the process change.
(g) Any owner or operator subject to the provisions of this subpart seeking to demonstrate compliance with §60.700(c)(4) shall use Method 2, 2A, 2C, or 2D of appendix A to 40 CFR part 60, as appropriate, for determination of volumetric flow rate.
(h) Each owner or operator seeking to demonstrate that a reactor process vent stream has a TOC concentration for compliance with the low concentration exemption in §60.700(c)(8) shall conduct an initial test to measure TOC concentration.
(1) The sampling site shall be selected as specified in paragraph (d)(1)(i) of this section.
(2) Method 18 of appendix A-6 or Method 25A of appendix A-7 to this part shall be used to measure concentration. ASTM D6420-18 (incorporated by reference, see §60.17) may be used in lieu of Method 18 as specified in paragraph (b)(4) of this section.
(3) Where Method 18 of appendix A-6 to this part, or ASTM D6420-18 (incorporated by reference, see §60.17) as specified in paragraph (b)(4) of this section, is used to qualify for the low concentration exclusion in §60.700(c)(8), the procedures in paragraphs (b)(4)(i) and (iv) of this section shall be used to measure TOC concentration, and the procedures of paragraph (b)(3) of this section shall be used to correct the TOC concentration to 3 percent oxygen. To qualify for the exclusion, the results must demonstrate that the concentration of TOC, corrected to 3 percent oxygen, is below 300 ppm by volume.
(4) Where Method 25A is used, the following procedures shall be used to calculate ppm by volume TOC concentration, corrected to 3 percent oxygen:
(i) Method 25A shall be used only if a single organic compound is greater than 50 percent of total TOC, by volume, in the reactor process vent stream. This compound shall be the principal organic compound.
(ii) The principal organic compound may be determined by either process knowledge or test data collected using an appropriate EPA Reference Method. Examples of information that could constitute process knowledge include calculations based on material balances, process stoichiometry, or previous test results provided the results are still relevant to the current reactor process vent stream conditions.
(iii) The principal organic compound shall be used as the calibration gas for Method 25A.
(iv) The span value for Method 25A shall be 300 ppmv.
(v) Use of Method 25A is acceptable if the response from the high-level calibration gas is at least 20 times the standard deviation of the response from the zero calibration gas when the instrument is zeroed on the most sensitive scale.
(vi) The owner or operator shall demonstrate that the concentration of TOC including methane and ethane measured by Method 25A, corrected to 3 percent oxygen, is below 150 ppm by volume to qualify for the low concentration exclusion in §60.700(c)(8).
(vii) The concentration of TOC shall be corrected to 3 percent oxygen using the procedures and equation in paragraph (b)(3) of this section.
[58 FR 45962, Aug. 31, 1993, as amended at 60 FR 58238, Nov. 27, 1995; 65 FR 61778, Oct. 17, 2000; 89 FR 43067, May 16, 2024]
§60.705 Reporting and recordkeeping requirements.
(a) Each owner or operator subject to §60.702 shall notify the Administrator of the specific provisions of §60.702 (§60.702 (a), (b), or (c)) with which the owner or operator has elected to comply. Notification shall be submitted with the notification of initial start-up required by §60.7(a)(3). If an owner or operator elects at a later date to use an alternative provision of §60.702 with which he or she will comply, then the Administrator shall be notified by the owner or operator 90 days before implementing a change and, upon implementing the change, a performance test shall be performed as specified by §60.704 no later than 180 days from initial start-up.
(b) Each owner or operator subject to the provisions of this subpart shall keep an up-to-date, readily accessible record of the following data measured during each performance test, and also include the following data in the report of the initial performance test required under §60.8. Where a boiler or process heater with a design heat input capacity of 44 MW (150 million Btu/hour) or greater is used or where the reactor process vent stream is introduced as the primary fuel to any size boiler or process heater to comply with §60.702(a), a report containing performance test data need not be submitted, but a report containing the information in paragraph (b)(2)(i) of this section is required. The same data specified in this section shall be submitted in the reports of all subsequently required performance tests where either the emission control efficiency of a combustion device, outlet concentration of TOC, or the TRE index value of a vent stream from a recovery system is determined. Beginning on July 15, 2024, owners and operators must submit the performance test report following the procedures specified in paragraph (u) of this section. Data collected using test methods that are supported by the EPA's Electronic Reporting Tool (ERT) as listed on the EPA's ERT website (https://www.epa.gov/electronic-reporting-air-emissions/electronic-reporting-tool-ert) at the time of the test must be submitted in a file format generated using the EPA's ERT. Alternatively, the owner or operator may submit an electronic file consistent with the extensible markup language (XML) schema listed on the EPA's ERT website. Data collected using test methods that are not supported by the EPA's ERT as listed on the EPA's ERT website at the time of the test must be included as an attachment in the ERT or an alternate electronic file.
(1) Where an owner or operator subject to the provisions of this subpart seeks to demonstrate compliance with §60.702(a) through use of either a thermal or catalytic incinerator:
(i) The average firebox temperature of the incinerator (or the average temperature upstream and downstream of the catalyst bed for a catalytic incinerator), measured at least every 15 minutes and averaged over the same time period of the performance testing, and
(ii) The percent reduction of TOC determined as specified in §60.704(b) achieved by the incinerator, or the concentration of TOC (ppmv, by compound) determined as specified in §60.704(b) at the outlet of the control device on a dry basis corrected to 3 percent oxygen.
(2) Where an owner or operator subject to the provisions of this subpart seeks to demonstrate compliance with §60.702(a) through use of a boiler or process heater:
(i) A description of the location at which the vent stream is introduced into the boiler or process heater, and
(ii) The average combustion temperature of the boiler or process heater with a design heat input capacity of less than 44 MW (150 million Btu/hr) measured at least every 15 minutes and averaged over the same time period of the performance testing.
(3) Where an owner or operator subject to the provisions of this subpart seeks to demonstrate compliance with §60.702(b) through use of a smokeless flare, flare design (i.e., steam-assisted, air-assisted or nonassisted), all visible emission readings, heat content determinations, flow rate measurements, and exit velocity determinations made during the performance test, continuous records of the flare pilot flame monitoring, and records of all periods of operations during which the pilot flame is absent.
(4) Where an owner or operator subject to the provisions of this subpart seeks to demonstrate compliance with §60.702(c):
(i) Where an absorber is the final recovery device in the recovery system, the exit specific gravity (or alternative parameter which is a measure of the degree of absorbing liquid saturation, if approved by the Administrator), and average exit temperature, of the absorbing liquid measured at least every 15 minutes and averaged over the same time period of the performance testing (both measured while the vent stream is normally routed and constituted); or
(ii) Where a condenser is the final recovery device in the recovery system, the average exit (product side) temperature measured at least every 15 minutes and averaged over the same time period of the performance testing while the vent stream is routed and constituted normally; or
(iii) Where a carbon adsorber is the final recovery device in the recovery system, the total steam mass flow measured at least every 15 minutes and averaged over the same time period of the performance test (full carbon bed cycle), temperature of the carbon bed after regeneration [and within 15 minutes of completion of any cooling cycle(s)], and duration of the carbon bed steaming cycle (all measured while the vent stream is routed and constituted normally); or
(iv) As an alternative to §60.705(b)(4) (i), (ii) or (iii), the concentration level or reading indicated by the organics monitoring device at the outlet of the absorber, condenser, or carbon adsorber, measured at least every 15 minutes and averaged over the same time period of the performance testing while the vent stream is normally routed and constituted.
(v) All measurements and calculations performed to determine the TRE index value of the vent stream.
(c) Each owner or operator subject to the provisions of this subpart shall keep up-to-date, readily accessible continuous records of the equipment operating parameters specified to be monitored under §60.703 (a) and (c) as well as up-to-date, readily accessible records of periods of operation during which the parameter boundaries established during the most recent performance test are exceeded. The Administrator may at any time require a report of these data. Where a combustion device is used to comply with §60.702(a), periods of operation during which the parameter boundaries established during the most recent performance tests are exceeded are defined as follows:
(1) For thermal incinerators, all 3-hour periods of operation during which the average combustion temperature was more than 28°C (50°F) below the average combustion temperature during the most recent performance test at which compliance with §60.702(a) was determined.
(2) For catalytic incinerators, all 3-hour periods of operation during which the average temperature of the vent stream immediately before the catalyst bed is more than 28°C (50°F) below the average temperature of the vent stream during the most recent performance test at which compliance with §60.702(a) was determined. The owner or operator also shall record all 3-hour periods of operation during which the average temperature difference across the catalyst bed is less than 80 percent of the average temperature difference of the bed during the most recent performance test at which compliance with §60.702(a) was determined.
(3) All 3-hour periods of operation during which the average combustion temperature was more than 28°C (50°F) below the average combustion temperature during the most recent performance test at which compliance with §60.702(a) was determined for boilers or process heaters with a design heat input capacity of less than 44 MW (150 million Btu/hr) where the vent stream is introduced with the combustion air or as a secondary fuel.
(4) For boilers or process heaters, whenever there is a change in the location at which the vent stream is introduced into the flame zone as required under §60.702(a).
(d) Each owner or operator subject to the provisions of this subpart shall keep records of the following:
(1) Up-to-date, readily accessible continuous records of the flow indication specified under §60.703(a)(2)(i), §60.703(b)(2)(i) and §60.703(c)(1)(i), as well as up-to-date, readily accessible records of all periods and the duration when the vent stream is diverted from the control device.
(2) Where a seal mechanism is used to comply with §60.703(a)(2)(ii), §60.703(b)(2)(ii), and §60.703(c)(1)(ii), a record of continuous flow is not required. In such cases, the owner or operator shall keep up-to-date, readily accessible records of all monthly visual inspections of the seals as well as readily accessible records of all periods and the duration when the seal mechanism is broken, the bypass line valve position has changed, the serial number of the broken car-seal has changed, or when the key for a lock-and-key type configuration has been checked out.
(e) Each owner or operator subject to the provisions of this subpart shall keep up-to-date, readily accessible continuous records of the flare pilot flame monitoring specified under §60.703(b), as well as up-to-date, readily accessible records of all periods of operations in which the pilot flame is absent.
(f) Each owner or operator subject to the provisions of this subpart shall keep up-to-date, readily accessible continuous records of the equipment operating parameters specified to be monitored under §60.703(d), as well as up-to-date, readily accessible records of periods of operation during which the parameter boundaries established during the most recent performance test are exceeded. The Administrator may at any time require a report of these data. Where an owner or operator seeks to comply with §60.702(c), periods of operation during which the parameter boundaries established during the most recent performance tests are exceeded are defined as follows:
(1) Where an absorber is the final recovery device in a recovery system, and where an organic compound monitoring device is not used:
(i) All 3-hour periods of operation during which the average absorbing liquid temperature was more than 11°C (20°F) above the average absorbing liquid temperature during the most recent performance test, or
(ii) All 3-hour periods of operation during which the average absorbing liquid specific gravity was more than 0.1 unit above, or more than 0.1 unit below, the average absorbing liquid specific gravity during the most recent performance test (unless monitoring of an alternative parameter, which is a measure of the degree of absorbing liquid saturation, is approved by the Administrator, in which case he will define appropriate parameter boundaries and periods of operation during which they are exceeded).
(2) Where a condenser is the final recovery device in a system, and where an organic compound monitoring device is not used, all 3-hour periods of operation during which the average exit (product side) condenser operating temperature was more than 6°C (11°F) above the average exit (product side) operating temperature during the most recent performance test.
(3) Where a carbon adsorber is the final recovery device in a system, and where an organic compound monitoring device is not used:
(i) All carbon bed regeneration cycles during which the total mass steam flow was more than 10 percent below the total mass steam flow during the most recent performance test, or
(ii) All carbon bed regeneration cycles during which the temperature of the carbon bed after regeneration (and after completion of any cooling cycle(s)) was more than 10 percent or 5°C greater, whichever is less stringent, than the carbon bed temperature (in degrees Celsius) during the most recent performance test.
(4) Where an absorber, condenser, or carbon adsorber is the final recovery device in the recovery system and where an organic compound monitoring device is used, all 3-hour periods of operation during which the average organic compound concentration level or reading of organic compounds in the exhaust gases is more than 20 percent greater than the exhaust gas organic compound concentration level or reading measured by the monitoring device during the most recent performance test.
(g) Each owner or operator of an affected facility subject to the provisions of this subpart and seeking to demonstrate compliance with §60.702(c) shall keep up-to-date, readily accessible records of:
(1) Any changes in production capacity, feedstock type, or catalyst type, or of any replacement, removal or addition of recovery equipment or reactors;
(2) Any recalculation of the TRE index value performed pursuant to §60.704(f); and
(3) The results of any performance test performed pursuant to the methods and procedures required by §60.704(d).
(h) Each owner or operator of an affected facility that seeks to comply with the requirements of this subpart by complying with the flow rate cutoff in §60.700(c)(4) shall keep up-to-date, readily accessible records to indicate that the vent stream flow rate is less than 0.011 scm/min and of any change in equipment or process operation that increases the operating vent stream flow rate, including a measurement of the new vent stream flow rate.
(i) Each owner or operator of an affected facility that seeks to comply with the requirements of this subpart by complying with the design production capacity provision in §60.700(c)(3) shall keep up-to-date, readily accessible records of any change in equipment or process operation that increases the design production capacity of the process unit in which the affected facility is located.
(j) Each owner or operator of an affected facility that seeks to comply with the requirements of this subpart by complying with the low concentration exemption in §60.700(c)(8) shall keep up-to-date, readily accessible records of any change in equipment or process operation that increases the concentration of the vent stream of the affected facility.
(k) Each owner or operator subject to the provisions of this subpart is exempt from the quarterly reporting requirements contained in §60.7(c) of the General Provisions.
(l) Each owner or operator that seeks to comply with the requirements of this subpart by complying with the requirements of §60.700(c)(2), (3), or (4) or §60.702 shall submit to the Administrator semiannual reports of the following recorded information. The initial report shall be submitted within 6 months after the initial start-up date. On and after July 15, 2025 or once the report template for this subpart has been available on the Compliance and Emissions Data Reporting Interface (CEDRI) website (https://www.epa.gov/electronic-reporting-air-emissions/cedri) for 1 year, whichever date is later, owners and operators must submit all subsequent reports using the appropriate electronic report template on the CEDRI website for this subpart and following the procedure specified in paragraph (u) of this section. The date report templates become available will be listed on the CEDRI website. Unless the Administrator or delegated state agency or other authority has approved a different schedule for submission of reports, the report must be submitted by the deadline specified in this subpart, regardless of the method in which the report is submitted.
(1) Exceedances of monitored parameters recorded under paragraphs (c), (f), and (g) of this section.
(2) All periods and duration recorded under paragraph (d) of this section when the vent stream is diverted from the control device to the atmosphere.
(3) All periods recorded under paragraph (e) of this section in which the pilot flame of the flare was absent.
(4) Any change in equipment or process operation that increases the operating vent stream flow rate above the low flow exemption level in §60.700(c)(4), including a measurement of the new vent stream flow rate, as recorded under paragraph (i) of this section. These must be reported as soon as possible after the change and no later than 180 days after the change. These reports may be submitted either in conjunction with semiannual reports or as a single separate report. A performance test must be completed within the same time period to verify the recalculated flow value and to obtain the vent stream characteristics of heating value and E TOC . The performance test is subject to the requirements of §60.8, and the performance test must be reported according to paragraph (b) of this section. Unless the facility qualifies for an exemption under any of the exemption provisions listed in §60.700(c), except for the total resource effectiveness index greater than 8.0 exemption in §60.700(c)(2), the facility must begin compliance with the requirements set forth in §60.702.
(5) Any change in equipment or process operation, as recorded under paragraph (i) of this section, that increases the design production capacity above the low capacity exemption level in §60.700(c)(3) and the new capacity resulting from the change for the reactor process unit containing the affected facility. These must be reported as soon as possible after the change and no later than 180 days after the change. These reports may be submitted either in conjunction with semiannual reports or as a single separate report. A performance test must be completed within the same time period to obtain the vent stream flow rate, heating value, and E TOC . The performance test is subject to the requirements of §60.8, and the performance test must be reported according to paragraph (b) of this section. The facility must begin compliance with the requirements set forth in §60.702 or §60.700(d). If the facility chooses to comply with §60.702, the facility may qualify for an exemption under §60.700(c)(2), (4), or (8).
(6) Any recalculation of the TRE index value, as recorded under paragraph (g) of this section.
(7) All periods recorded under paragraph (d) of this section in which the seal mechanism is broken or the by-pass line valve position has changed. A record of the serial number of the car-seal or a record to show that the key to unlock the bypass line valve was checked out must be maintained to demonstrate the period, the duration, and frequency in which the bypass line was operated.
(8) Any change in equipment or process operation that increases the vent stream concentration above the low concentration exemption level in §60.700(c)(8), including a measurement of the new vent stream concentration, as recorded under paragraph (j) of this section. These must be reported as soon as possible after the change and no later than 180 days after the change. These reports may be submitted either in conjunction with semiannual reports or as a single separate report. If the vent stream concentration is above 300 ppmv as measured using Method 18 of appendix A-6 to this part, or ASTM D6420-18 (incorporated by reference, see §60.17) as specified in §60.704(b)(4), or above 150 ppmv as measured using Method 25A of appendix A-7 to this part, a performance test must be completed within the same time period to obtain the vent stream flow rate, heating value, and ETOC. The performance test is subject to the requirements of §60.8, and the performance test must be reported according to paragraph (b) of this section. Unless the facility qualifies for an exemption under any of the exemption provisions listed in §60.700(c), except for the TRE index greater than 8.0 exemption in §60.700(c)(2), the facility must begin compliance with the requirements set forth in §60.702.
(m) The requirements of paragraph (l) of this section remain in force until and unless EPA, in delegating enforcement authority to a State under section 111(c) of the Act, approves reporting requirements or an alternative means of compliance surveillance adopted by such State. In that event, affected sources within the State will be relieved of the obligation to comply with paragraph (l), provided that they comply with the requirements established by the State. The EPA will not approve a waiver of electronic reporting to the EPA in delegating enforcement authority. Thus, electronic reporting to the EPA cannot be waived, and as such, the provisions of this paragraph cannot be used to relieve owners or operators of affected facilities of the requirement to submit the electronic reports required in this section to the EPA.
(n) Each owner or operator that seeks to demonstrate compliance with §60.700(c)(3) must submit to the Administrator an initial report detailing the design production capacity of the process unit.
(o) Each owner or operator that seeks to demonstrate compliance with §60.700(c)(4) must submit to the Administrator an initial report including a flow rate measurement using the test methods specified in §60.704.
(p) Each owner or operator that seeks to demonstrate compliance with §60.700(c)(8) must submit to the Administrator an initial report including a concentration measurement using the test method specified in §60.704.
(q) The Administrator will specify appropriate reporting and recordkeeping requirements where the owner or operator of an affected facility complies with the standards specified under §60.702 other than as provided under §60.703 (a), (b), (c), and (d).
(r) Each owner or operator whose reactor process vent stream is routed to a distillation unit subject to subpart NNN and who seeks to demonstrate compliance with §60.700(c)(5) shall submit to the Administrator a process design description as part of the initial report. This process design description must be retained for the life of the process. No other records or reports would be required unless process changes are made.
(s) Each owner or operator who seeks to demonstrate compliance with §60.702 (a) or (b) using a control device must maintain on file a schematic diagram of the affected vent streams, collection system(s), fuel systems, control devices, and bypass systems as part of the initial report. This schematic diagram must be retained for the life of the system.
(t) Each owner or operator that seeks to demonstrate compliance with §60.700(c)(2) must maintain a record of the initial test for determining the total resource effectiveness index and the results of the initial total resource effectiveness index calculation.
(u) If an owner or operator is required to submit notifications or reports following the procedure specified in this paragraph (u), the owner or operator must submit notifications or reports to the EPA via CEDRI, which can be accessed through the EPA's Central Data Exchange (CDX) (https://cdx.epa.gov/). The EPA will make all the information submitted through CEDRI available to the public without further notice to the owner or operator. Do not use CEDRI to submit information the owner or operator claims as CBI. Although the EPA does not expect persons to assert a claim of CBI, if an owner or operator wishes to assert a CBI claim for some of the information in the report or notification, the owner or operator must submit a complete file in the format specified in this subpart, including information claimed to be CBI, to the EPA following the procedures in paragraphs (u)(1) and (2) of this section. Clearly mark the part or all of the information claimed to be CBI. Information not marked as CBI may be authorized for public release without prior notice. Information marked as CBI will not be disclosed except in accordance with procedures set forth in 40 CFR part 2. All CBI claims must be asserted at the time of submission. Anything submitted using CEDRI cannot later be claimed CBI. Furthermore, under CAA section 114(c), emissions data is not entitled to confidential treatment, and the EPA is required to make emissions data available to the public. Thus, emissions data will not be protected as CBI and will be made publicly available. The owner or operator must submit the same file submitted to the CBI office with the CBI omitted to the EPA via the EPA's CDX as described earlier in this paragraph (u).
(1) The preferred method to receive CBI is for it to be transmitted electronically using email attachments, File Transfer Protocol, or other online file sharing services. Electronic submissions must be transmitted directly to the OAQPS CBI Office at the email address oaqpscbi@epa.gov, and as described above, should include clear CBI markings. ERT files should be flagged to the attention of the Group Leader, Measurement Policy Group; all other files should be flagged to the attention of the SOCMI NSPS Sector Lead. Owners and operators who do not have their own file sharing service and who require assistance with submitting large electronic files that exceed the file size limit for email attachments should email oaqpscbi@epa.gov to request a file transfer link.
(2) If an owner or operator cannot transmit the file electronically, the owner or operator may send CBI information through the postal service to the following address: OAQPS Document Control Officer (C404-02), OAQPS, U.S. Environmental Protection Agency, 109 T.W. Alexander Drive, P.O. Box 12055, Research Triangle Park, North Carolina 27711. ERT files should be sent to the attention of the Group Leader, Measurement Policy Group, and all other files should be sent to the attention of the SOCMI NSPS Sector Lead. The mailed CBI material should be double wrapped and clearly marked. Any CBI markings should not show through the outer envelope.
(v) Owners and operators required to electronically submit notifications or reports through CEDRI in the EPA's CDX may assert a claim of EPA system outage for failure to timely comply with the electronic submittal requirement. To assert a claim of EPA system outage, owners and operators must meet the requirements outlined in paragraphs (v)(1) through (7) of this section.
(1) The owner or operator must have been or will be precluded from accessing CEDRI and submitting a required report within the time prescribed due to an outage of either the EPA's CEDRI or CDX systems.
(2) The outage must have occurred within the period of time beginning five business days prior to the date that the submission is due.
(3) The outage may be planned or unplanned.
(4) The owner or operator must submit notification to the Administrator in writing as soon as possible following the date the owner or operator first knew, or through due diligence should have known, that the event may cause or has caused a delay in reporting.
(5) The owner or operator must provide to the Administrator a written description identifying:
(i) The date(s) and time(s) when CDX or CEDRI was accessed and the system was unavailable;
(ii) A rationale for attributing the delay in reporting beyond the regulatory deadline to EPA system outage;
(iii) A description of measures taken or to be taken to minimize the delay in reporting; and
(iv) The date by which the owner or operator proposes to report, or if the owner or operator has already met the reporting requirement at the time of the notification, the date the report was submitted.
(6) The decision to accept the claim of EPA system outage and allow an extension to the reporting deadline is solely within the discretion of the Administrator.
(7) In any circumstance, the report must be submitted electronically as soon as possible after the outage is resolved.
(w) Owners and operators required to electronically submit notifications or reports through CEDRI in the EPA's CDX may assert a claim of force majeure for failure to timely comply with the electronic submittal requirement. To assert a claim of force majeure, owners and operators must meet the requirements outlined in paragraphs (w)(1) through (5) of this section.
(1) An owner or operator may submit a claim if a force majeure event is about to occur, occurs, or has occurred or there are lingering effects from such an event within the period of time beginning five business days prior to the date the submission is due. For the purposes of this section, a force majeure event is defined as an event that will be or has been caused by circumstances beyond the control of the affected facility, its contractors, or any entity controlled by the affected facility that prevents the owner or operator from complying with the requirement to submit a report electronically within the time period prescribed. Examples of such events are acts of nature (e.g., hurricanes, earthquakes, or floods), acts of war or terrorism, or equipment failure or safety hazard beyond the control of the affected facility (e.g., large scale power outage).
(2) The owner or operator must submit notification to the Administrator in writing as soon as possible following the date the owner or operator first knew, or through due diligence should have known, that the event may cause or has caused a delay in reporting.
(3) The owner or operator must provide to the Administrator:
(i) A written description of the force majeure event;
(ii) A rationale for attributing the delay in reporting beyond the regulatory deadline to the force majeure event;
(iii) A description of measures taken or to be taken to minimize the delay in reporting; and
(iv) The date by which the owner or operator proposes to report, or if the owner or operator has already met the reporting requirement at the time of the notification, the date the report was submitted.
(4) The decision to accept the claim of force majeure and allow an extension to the reporting deadline is solely within the discretion of the Administrator.
(5) In any circumstance, the reporting must occur as soon as possible after the force majeure event occurs.
[58 FR 45962, Aug. 31, 1993, as amended at 60 FR 58238, Nov. 27, 1995; 65 FR 78279, Dec. 14, 2000; 89 FR 43067, May 16, 2024]
§60.706 Reconstruction.
(a) For purposes of this subpart “fixed capital cost of the new components,” as used in §60.15, includes the fixed capital cost of all depreciable components which are or will be replaced pursuant to all continuous programs of component replacement which are commenced within any 2-year period following June 29, 1990. For purposes of this paragraph, “commenced” means that an owner or operator has undertaken a continuous program of component replacement or that an owner or operator has entered into a contractual obligation to undertake and complete, within a reasonable time, a continuous program of component replacement.
(b) [Reserved]
§60.707 Chemicals affected by subpart RRR.
Chemical | CAS No. 1 |
---|---|
1 CAS numbers refer to the Chemical Abstracts Registry numbers assigned to specific chemicals, isomers, or mixtures of chemicals. Some isomers or mixtures that are covered by the standards do not have CAS numbers assigned to them. The standards apply to all of the chemicals listed, whether CAS numbers have been assigned or not. | |
Acetaldehyde | 75-07-0 |
Acetic acid | 64-19-7 |
Acetic anhydride | 108-24-7 |
Acetone | 67-64-1 |
Acetone cyanohydrin | 75-86-5 |
Acetylene | 74-86-2 |
Acrylic acid | 79-10-7 |
Acrylonitrile | 107-13-1 |
Adipic acid | 124-04-9 |
Adiponitrile | 111-69-3 |
Alcohols, C-11 or lower, mixtures | |
Alcohols, C-12 or higher, mixtures | |
Alcohols, C-12 or higher, unmixed | |
Allyl chloride | 107-05-1 |
Amylene | 513-35-9 |
Amylenes, mixed | |
Aniline | 62-53-3 |
Benzene | 71-43-2 |
Benzenesulfonic acid | 98-11-3 |
Benzenesulfonic acid C10-16-alkyl derivatives, sodium salts | 68081-81-2 |
Benzyl chloride | 100-44-7 |
Bisphenol A | 80-05-7 |
Brometone | 76-08-4 |
1,3-Butadiene | 106-99-0 |
Butadiene and butene fractions | |
n-Butane | 106-97-8 |
1,4-Butanediol | 110-63-4 |
Butanes, mixed | |
1-Butene | 106-98-9 |
2-Butene | 25167-67-3 |
Butenes, mixed | |
n-Butyl acetate | 123-86-4 |
Butyl acrylate | 141-32-2 |
n-Butyl alcohol | 71-36-3 |
sec-Butyl alcohol | 78-92-2 |
tert-Butyl alcohol | 75-65-0 |
Butylbenzyl phthalate | 85-68-7 |
tert-Butyl hydroperoxide | 75-91-2 |
2-Butyne-1,4-diol | 110-65-6 |
Butyraldehyde | 123-72-8 |
Butyric anhydride | 106-31-0 |
Caprolactam | 105-60-2 |
Carbon disulfide | 75-15-0 |
Carbon tetrachloride | 56-23-5 |
Chloroacetic acid | 79-11-8 |
Chlorobenzene | 108-90-7 |
Chlorodifluoromethane | 75-45-6 |
Chloroform | 67-66-3 |
p-Chloronitrobenzene | 100-00-5 |
Citric acid | 77-92-9 |
Cumene | 98-82-8 |
Cumene hydroperoxide | 80-15-9 |
Cyanuric chloride | 108-77-0 |
Cyclohexane | 110-82-7 |
Cyclohexane, oxidized | 68512-15-2 |
Cyclohexanol | 108-93-0 |
Cyclohexanone | 108-94-1 |
Cyclohexanone oxime | 100-64-1 |
Cyclohexene | 110-83-8 |
Cyclopropane | 75-19-4 |
Diacetone alcohol | 123-42-2 |
1,4-Dichlorobutene | 110-57-6 |
3,4-Dichloro-1-butene | 64037-54-3 |
Dichlorodifluoromethane | 75-71-8 |
Dichlorodimethylsilane | 75-78-5 |
Dichlorofluoromethane | 75-43-4 |
Diethanolamine | 111-42-2 |
Diethylbenzene | 25340-17-4 |
Diethylene glycol | 111-46-6 |
Di-isodecyl phthalate | 26761-40-0 |
Dimethyl terephthalate | 120-61-6 |
2,4-(and 2,6)-dinitrotoluene | 121-14-2 |
606-20-2 | |
Dioctyl phthalate | 117-81-7 |
Dodecene | 25378-22-7 |
Dodecylbenzene, nonlinear | |
Dodecylbenzenesulfonic acid | 27176-87-0 |
Dodecylbenzenesulfonic acid, sodium salt | 25155-30-0 |
Epichlorohydrin | 106-89-8 |
Ethanol | 64-17-5 |
Ethanolamine | 141-43-5 |
Ethyl acetate | 141-78-6 |
Ethyl acrylate | 140-88-5 |
Ethylbenzene | 100-41-4 |
Ethyl chloride | 75-00-3 |
Ethylene | 74-85-1 |
Ethylene dibromide | 106-93-4 |
Ethylene dichloride | 107-06-2 |
Ethylene glycol | 107-21-1 |
Ethylene glycol monobutyl ether | 111-76-2 |
Ethylene glycol monoethyl ether acetate | 111-15-9 |
Ethylene glycol monomethyl ether | 109-86-4 |
Ethylene oxide | 75-21-8 |
2-Ethylhexyl alcohol | 104-76-7 |
(2-Ethylhexyl) amine | 104-75-6 |
6-Ethyl-1,2,3,4-tetrahydro 9,10-anthracenedione | 15547-17-8 |
Formaldehyde | 50-00-0 |
Glycerol | 56-81-5 |
n-Heptane | 142-82-5 |
Heptenes (mixed) | |
Hexamethylene diamine | 124-09-4 |
Hexamethylene diamine adipate | 3323-53-3 |
Hexamethylenetetramine | 100-97-0 |
Hexane | 110-54-3 |
Isobutane | 75-28-5 |
Isobutanol | 78-83-1 |
Isobutylene | 115-11-7 |
Isobutyraldehyde | 78-84-2 |
Isopentane | 78-78-4 |
Isoprene | 78-79-5 |
Isopropanol | 67-63-0 |
Ketene | 463-51-4 |
Linear alcohols, ethoxylated, mixed | |
Linear alcohols, ethoxylated, and sulfated, sodium salt, mixed | |
Linear alcohols, sulfated, sodium salt, mixed | |
Linear alkylbenzene | 123-01-3 |
Maleic anhydride | 108-31-6 |
Mesityl oxide | 141-79-7 |
Methanol | 67-56-1 |
Methylamine | 74-39-5 |
ar-Methylbenzenediamine | 25376-45-8 |
Methyl chloride | 74-87-3 |
Methylene chloride | 75-09-2 |
Methyl ethyl ketone | 78-93-3 |
Methyl isobutyl ketone | 108-10-1 |
Methyl methacrylate | 80-62-6 |
1-Methyl-2-pyrrolidone | 872-50-4 |
Methyl tert-butyl ether | |
Naphthalene | 91-20-3 |
Nitrobenzene | 98-95-3 |
1-Nonene | 27215-95-8 |
Nonyl alcohol | 143-08-8 |
Nonylphenol | 25154-52-3 |
Nonylphenol, ethoxylated | 9016-45-9 |
Octene | 25377-83-7 |
Oil-soluble petroleum sulfonate, calcium salt | |
Pentaerythritol | 115-77-5 |
3-Pentenenitrile | 4635-87-4 |
Pentenes, mixed | 109-67-1 |
Perchloroethylene | 127-18-4 |
Phenol | 108-95-2 |
1-Phenylethyl hydroperoxide | 3071-32-7 |
Phenylpropane | 103-65-1 |
Phosgene | 75-44-5 |
Phthalic anhydride | 85-44-9 |
Propane | 74-98-6 |
Propionaldehyde | 123-38-6 |
Propyl alcohol | 71-23-8 |
Propylene | 115-07-1 |
Propylene glycol | 57-55-6 |
Propylene oxide | 75-56-9 |
Sorbitol | 50-70-4 |
Styrene | 100-42-5 |
Terephthalic acid | 100-21-0 |
Tetraethyl lead | 78-00-2 |
Tetrahydrofuran | 109-99-9 |
Tetra (methyl-ethyl) lead | |
Tetramethyl lead | 75-74-1 |
Toluene | 108-88-3 |
Toluene-2,4-diamine | 95-80-7 |
Toluene-2,4-(and, 2,6)-diisocyanate (80/20 mixture) | 26471-62-5 |
1,1,1-Trichloroethane | 71-55-6 |
1,1,2-Trichloroethane | 79-00-5 |
Trichloroethylene | 79-01-6 |
Trichlorofluoromethane | 75-69-4 |
1,1,2-Trichloro-1,2,2-trifluoroethane | 76-13-1 |
Triethanolamine | 102-71-6 |
Triethylene glycol | 112-27-6 |
Vinyl acetate | 108-05-4 |
Vinyl chloride | 75-01-4 |
Vinylidene chloride | 75-35-4 |
m-Xylene | 108-38-3 |
o-Xylene | 95-47-6 |
p-Xylene | 106-42-3 |
Xylenes (mixed) | 1330-20-7 |
[58 FR 45962, Aug. 31, 1993, as amended at 60 FR 58238, Nov. 27, 1995]
§60.708 Delegation of authority.
(a) In delegating implementation and enforcement authority to a State under section 111(c) of the Act, the authorities contained in paragraph (b) of this section shall be retained by the Administrator and not transferred to a State.
(b) Authorities which will not be delegated to States: §60.703(e) and approval of an alternative to any electronic reporting to the EPA required by this subpart.
[89 FR 43067, May 16, 2024]
READ MORESHOW LESS
['Air Programs']
['Air Quality']
Load More
J. J. Keller is the trusted source for DOT / Transportation, OSHA / Workplace Safety, Human Resources, Construction Safety and Hazmat / Hazardous Materials regulation compliance products and services. J. J. Keller helps you increase safety awareness, reduce risk, follow best practices, improve safety training, and stay current with changing regulations.
Copyright 2024 J. J. Keller & Associate, Inc. For re-use options please contact copyright@jjkeller.com or call 800-558-5011.