['Hazardous Materials Safety - OSHA']
['Compressed Gases']
05/05/2022
...
Standard Number: 1910.101
November 8, 1988
Mr. Jack Cannova
Tempe Industrial Supply
412 Orion Street
Tempe, AZ 95283
Dear Mr. Cannova:
With regard to the use of plastic pipe for unprotected, above ground gas transmission and distribution piping systems, it is our understanding that only one type of plastic pipe is acceptable for such uses. That pipe, Acrylonitrile-Butadiene-Styrene (ABS), is marked on the pipe as approved for compressed air supply. Otherwise, the above ground portion of such a system must be enclosed in a conduit or casing of sufficient strength to provide protection from external damage and deterioration.
Hopefully the above information satisfies your request of October 27, 1988.
Sincerely,
TIM ARBOGAST, Director
[Corrected 10/22/2004]
['Hazardous Materials Safety - OSHA']
['Compressed Gases']
UPGRADE TO CONTINUE READING
Load More
J. J. Keller is the trusted source for DOT / Transportation, OSHA / Workplace Safety, Human Resources, Construction Safety and Hazmat / Hazardous Materials regulation compliance products and services. J. J. Keller helps you increase safety awareness, reduce risk, follow best practices, improve safety training, and stay current with changing regulations.