['Air Programs']
['Air Quality']
02/04/2025
...
Table 1 of Subpart TTTT of Part 60
Affected EGU | CO 2 Emission standard |
---|---|
Newly constructed steam generating unit or integrated gasification combined cycle (IGCC) | 640 kg CO 2 /MWh of gross energy output (1,400 lb CO 2 /MWh-gross). |
Reconstructed steam generating unit or IGCC that has base load rating of 2,100 GJ/h (2,000 MMBtu/h) or less | 910 kg CO 2 /MWh of gross energy output (2,000 lb CO 2 /MWh-gross). |
Reconstructed steam generating unit or IGCC that has a base load rating greater than 2,100 GJ/h (2,000 MMBtu/h) | 820 kg CO 2 /MWh of gross energy output (1,800 lb CO 2 /MWh-gross). |
Modified steam generating unit or IGCC | A unit-specific emission limit determined by the unit's best historical annual CO 2 emission rate (from 2002 to the date of the modification); the emission limit will be no lower than: |
(1) 820 kg CO 2 /MWh of gross energy output (1,800 lb CO 2 /MWh-gross) for units with a base load rating greater than 2,100 GJ/h (2,000 MMBtu/h); or | |
(2) 910 kg CO 2 /MWh of gross energy output (2,000 lb CO 2 /MWh-gross) for units with a base load rating of 2,100 GJ/h (2,000 MMBtu/h) or less. |
[89 FR 40034, May 9, 2024]
Table 2 of Subpart TTTT of Part 60
Affected EGU | CO 2 Emission standard |
---|---|
Newly constructed or reconstructed stationary combustion turbine that supplies more than its design efficiency or 50 percent, whichever is less, times its potential electric output as net-electric sales on both a 12-operating month and a 3-year rolling average basis and combusts more than 90% natural gas on a heat input basis on a 12-operating-month rolling average basis | 450 kg CO 2 /MWh (1,000 lb CO 2 /MWh) of gross energy output; or 470 kg CO 2 /MWh (1,030 lb CO 2 /MWh) of net energy output. |
Newly constructed or reconstructed stationary combustion turbine that supplies its design efficiency or 50 percent, whichever is less, times its potential electric output or less as net-electric sales on either a 12-operating month or a 3-year rolling average basis and combusts more than 90% natural gas on a heat input basis on a 12-operating-month rolling average basis] | 50 kg CO 2 /GJ (120 lb CO 2 /MMBtu) of heat input. |
Newly constructed and reconstructed stationary combustion turbine that combusts 90% or less natural gas on a heat input basis on a 12-operating-month rolling average basis | Between 50 to 69 kg CO 2 /GJ (120 to 160 lb CO 2 /MMBtu) of heat input as determined by the procedures in §60.5525. |
[89 FR 40034, May 9, 2024]
Table 3 to Subpart TTTT of Part 60
General provisions citation | Subject of citation | Applies to subpart TTTT | Explanation |
---|---|---|---|
§60.1 | Applicability | Yes | |
§60.2 | Definitions | Yes | Additional terms defined in §60.5580. |
§60.3 | Units and Abbreviations | Yes | |
§60.4 | Address | Yes | Does not apply to information reported electronically through ECMPS. Duplicate submittals are not required. |
§60.5 | Determination of construction or modification | Yes | |
§60.6 | Review of plans | Yes | |
§60.7 | Notification and Recordkeeping | Yes | Only the requirements to submit the notifications in §60.7(a)(1) and (3) and to keep records of malfunctions in §60.7(b), if applicable. |
§60.8(a) | Performance tests | No | |
§60.8(b) | Performance test method alternatives | Yes | Administrator can approve alternate methods |
§60.8(c)-(f) | Conducting performance tests | No | |
§60.9 | Availability of Information | Yes | |
§60.10 | State authority | Yes | |
§60.11 | Compliance with standards and maintenance requirements | No. | |
§60.12 | Circumvention | Yes | |
§60.13 (a)-(h), (j) | Monitoring requirements | No | All monitoring is done according to part 75. |
§60.13 (i) | Monitoring requirements | Yes | Administrator can approve alternative monitoring procedures or requirements |
§60.14 | Modification | Yes (steam generating units and IGCC facilities) No (stationary combustion turbines) | |
§60.15 | Reconstruction | Yes | |
§60.16 | Priority list | No | |
§60.17 | Incorporations by reference | Yes | |
§60.18 | General control device requirements | No | |
§60.19 | General notification and reporting requirements | Yes | Does not apply to notifications under §75.61 or to information reported through ECMPS. |
[89 FR 40035, May 9, 2024]
READ MORESHOW LESS
['Air Programs']
['Air Quality']
Load More
J. J. Keller is the trusted source for DOT / Transportation, OSHA / Workplace Safety, Human Resources, Construction Safety and Hazmat / Hazardous Materials regulation compliance products and services. J. J. Keller helps you increase safety awareness, reduce risk, follow best practices, improve safety training, and stay current with changing regulations.