Category: | Emergency action plans |
Requirement: | An emergency action plan must be in writing, kept in the workplace, and available to employees for review. However, an employer with 10 or fewer employees may communicate the plan orally to employees. |
Regulation: | 1910.38(b) |
|
Category: | Fire prevention plans |
Requirement: | A fire prevention plan must be in writing, be kept in the workplace, and be made available to employees for review. However, an employer with 10 or fewer employees may communicate the plan orally to employees. |
Regulation: | 1910.39(b) |
|
Category: | Flammable and combustible liquids - tank storage |
Requirement: | Tanks designed for underground service not exceeding 2,500 gallons capacity may be used above ground. |
Regulation: | 1910.106(b)(1)(iii)(b) |
|
Category: | Flammable and combustible liquids - container and portable tank storage |
Requirement: | Not more than 60 gallons of Class I or Class II liquids, nor more than 120 gallons of Class III liquids may be stored in a storage cabinet. |
Regulation: | 1910.106(d)(3)(i) |
|
Category: | Flammable and combustible liquids - container and portable tank storage |
Requirement: | Containers over 30 gallons capacity shall not be stacked one upon the other. |
Regulation: | 1910.106(d)(4)(v) |
|
Category: | Flammable and combustible liquids - industrial
plants |
Requirement: | The quantity of liquid that may be located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building shall not exceed:
(1) 25 gallons of Class IA liquids in containers
(2) 120 gallons of Class IB, IC, II, or III liquids in
containers
(3) 660 gallons of Class IB, IC, II, or III liquids in a single portable tank. |
Regulation: | 1910.106(e)(2)(ii)(b) |
|
Category: | 1904 - Recording and Reporting Occupational Injuries and Illnesses |
Requirement: | If your company had ten (10) or fewer employees at all times during the last calendar year, you do not need to keep OSHA injury and illness records unless OSHA or the BLS informs you in writing that you must keep records under 1904.41 or 1904.42. |
Regulation: | 1904.1(a)(1) |
|
Category: | Spray finishing using flammable and combustible
materials |
Requirement: | The spraying operations except electrostatic spraying operations shall be so designed, installed and maintained that the average air velocity over the open face of the booth (or booth cross section during spraying operations) shall not be less than 100 linear feet per minute. Electrostatic spraying operations may be conducted with an air velocity over the open face of the booth of not less than 60 linear feet per minute, or more, depending on the volume of the finishing material being applied and its flammability and explosion characteristics. |
Regulation: | 1910.107(b)(5)(i) |
| |
Category: | Spray finishing using flammable and combustible
materials |
Requirement: | The quantity of flammable or combustible liquids kept in the vicinity of spraying operations shall be the minimum required for operations and should ordinarily not exceed a supply for 1 day or one shift. |
Regulation: | 1910.107(e)(2) |
|