You must keep five types of records:
(a) Materials separation plan and siting analysis.
(b) Operator training and certification.
(c) Stack tests.
(d) Continuously monitored pollutants and parameters.
(e) Carbon feed rate.
(a) Keep all records onsite in paper copy or electronic format unless the Administrator approves another format.
(b) Keep all records on each municipal waste combustion unit for at least 5 years.
(c) Make all records available for submittal to the Administrator, or for onsite review by an inspector.
You must keep records of five items:
(a) The date of each record.
(b) The final materials separation plan.
(c) The siting analysis.
(d) A record of the location and date of the public meetings.
(e) Your responses to the public comments received during the public comment periods.
You must keep records of six items:
(a) Records of provisional certifications. Include three items:
(1) For your municipal waste combustion plant, names of the chief facility operator, shift supervisors, and control room operators who are provisionally certified by the American Society of Mechanical Engineers or an equivalent State-approved certification program.
(2) Dates of the initial provisional certifications.
(3) Documentation showing current provisional certifications.
(b) Records of full certifications. Include three items:
(1) For your municipal waste combustion plant, names of the chief facility operator, shift supervisors, and control room operators who are fully certified by the American Society of Mechanical Engineers or an equivalent State-approved certification program.
(2) Dates of initial and renewal full certifications.
(3) Documentation showing current full certifications.
(c) Records showing completion of the operator training course. Include three items:
(1) For your municipal waste combustion plant, names of the chief facility operator, shift supervisors, and control room operators who have completed the EPA or State municipal waste combustion operator training course.
(2) Dates of completion of the operator training course.
(3) Documentation showing completion of the operator training course.
(d) Records of reviews for plant-specific operating manuals. Include three items:
(1) Names of persons who have reviewed the operating manual.
(2) Date of the initial review.
(3) Dates of subsequent annual reviews.
(e) Records of when a certified operator is temporarily offsite. Include two main items:
(1) If the certified chief facility operator and certified shift supervisor are offsite for more than 12 hours, but for 2 weeks or less, and no other certified operator is onsite, record the dates that the certified chief facility operator and certified shift supervisor were offsite.
(2) When the certified chief facility operator and certified shift supervisor are offsite for more than 2 weeks and no other certified operator is onsite, keep records of four items:
(i) Your notice that all certified persons are offsite.
(ii) The conditions that cause those people to be offsite.
(iii) The corrective actions you are taking to ensure a certified chief facility operator or certified shift supervisor is onsite.
(iv) Copies of the written reports submitted every 4 weeks that summarize the actions taken to ensure that a certified chief facility operator or certified shift supervisor will be onsite.
(f) Records of calendar dates. Include the calendar date on each record.
For stack tests required under §60.1285, you must keep records of four items:
(a) The results of the stack tests for eight pollutants or parameters recorded in the appropriate units of measure specified in table 1 of this subpart:
(1) Dioxins/furans.
(2) Cadmium.
(3) Lead.
(4) Mercury.
(5) Opacity.
(6) Particulate matter.
(7) Hydrogen chloride.
(8) Fugitive ash.
(b) Test reports including supporting calculations that document the results of all stack tests.
(c) The maximum demonstrated load of your municipal waste combustion units and maximum temperature at the inlet of your particulate matter control device during all stack tests for dioxins/furans emissions.
(d) The calendar date of each record.
You must keep records of eight items:
(a) Records of monitoring data. Document six parameters measured using continuous monitoring systems:
(1) All 6-minute average levels of opacity.
(2) All 1-hour average concentrations of sulfur dioxide emissions.
(3) For Class I municipal waste combustion units only, all 1-hour average concentrations of nitrogen oxides emissions.
(4) All 1-hour average concentrations of carbon monoxide emissions.
(5) All 1-hour average load levels of your municipal waste combustion unit.
(6) All 1-hour average flue gas temperatures at the inlet of the particulate matter control device.
(b) Records of average concentrations and percent reductions. Document five parameters:
(1) All 24-hour daily block geometric average concentrations of sulfur dioxide emissions or average percent reductions of sulfur dioxide emissions.
(2) For Class I municipal waste combustion units only, all 24-hour daily arithmetic average concentrations of nitrogen oxides emissions.
(3) All 4-hour block or 24-hour daily block arithmetic average concentrations of carbon monoxide emissions.
(4) All 4-hour block arithmetic average load levels of your municipal waste combustion unit.
(5) All 4-hour block arithmetic average flue gas temperatures at the inlet of the particulate matter control device.
(c) Records of exceedances. Document three items:
(1) Calendar dates whenever any of the five pollutant or parameter levels recorded in paragraph (b) of this section or the opacity level recorded in paragraph (a)(1) of this section did not meet the emission limits or operating levels specified in this subpart.
(2) Reasons you exceeded the applicable emission limits or operating levels.
(3) Corrective actions you took, or are taking, to meet the emission limits or operating levels.
(d) Records of minimum data. Document three items:
(1) Calendar dates for which you did not collect the minimum amount of data required under §§60.1260 and 60.1335. Record the dates for five types of pollutants and parameters:
(i) Sulfur dioxide emissions.
(ii) For Class I municipal waste combustion units only, nitrogen oxides emissions.
(iii) Carbon monoxide emissions.
(iv) Load levels of your municipal waste combustion unit.
(v) Temperatures of the flue gases at the inlet of the particulate matter control device.
(2) Reasons you did not collect the minimum data.
(3) Corrective actions you took, or are taking, to obtain the required amount of data.
(e) Records of exclusions. Document each time you have excluded data from your calculation of averages for any of the following five pollutants or parameters and the reasons the data were excluded:
(1) Sulfur dioxide emissions.
(2) For Class I municipal waste combustion units only, nitrogen oxides emissions.
(3) Carbon monoxide emissions.
(4) Load levels of your municipal waste combustion unit.
(5) Temperatures of the flue gases at the inlet of the particulate matter control device.
(f) Records of drift and accuracy. Document the results of your daily drift tests and quarterly accuracy determinations according to Procedure 1 of appendix F of this part. Keep the records for the sulfur dioxide, nitrogen oxides (Class I municipal waste combustion units only), and carbon monoxide continuous emissions monitoring systems.
(g) Records of the relationship between oxygen and carbon dioxide. If you choose to monitor carbon dioxide instead of oxygen as a diluent gas, document the relationship between oxygen and carbon dioxide, as specified in §60.1255.
(h) Records of calendar dates. Include the calendar date on each record.
For municipal waste combustion units that use activated carbon to control dioxins/furans or mercury emissions, you must keep records of five items:
(a) Records of average carbon feed rate. Document five items:
(1) Average carbon feed rate in kilograms (or pounds) per hour during all stack tests for dioxins/furans and mercury emissions. Include supporting calculations in the records.
(2) For the operating parameter chosen to monitor carbon feed rate, average operating level during all stack tests for dioxins/furans and mercury emissions. Include supporting data that document the relationship between the operating parameter and the carbon feed rate.
(3) All 8-hour block average carbon feed rates in kilograms (or pounds) per hour calculated from the monitored operating parameter.
(4) Total carbon purchased and delivered to the municipal waste combustion plant for each calendar quarter. If you choose to evaluate total carbon purchased and delivered on a municipal waste combustion unit basis, record the total carbon purchased and delivered for each individual municipal waste combustion unit at your plant. Include supporting documentation.
(5) Required quarterly usage of carbon for the municipal waste combustion plant, calculated using equation 4 or 5 in §60.1460(f). If you choose to evaluate required quarterly usage for carbon on a municipal waste combustion unit basis, record the required quarterly usage for each municipal waste combustion unit at your plant. Include supporting calculations.
(b) Records of low carbon feed rates. Document three items:
(1) The calendar dates when the average carbon feed rate over an 8-hour block was less than the average carbon feed rates determined during the most recent stack test for dioxins/furans or mercury emissions (whichever has a higher feed rate).
(2) Reasons for the low carbon feed rates.
(3) Corrective actions you took or are taking to meet the 8-hour average carbon feed rate requirement.
(c) Records of minimum carbon feed rate data. Document three items:
(1) Calendar dates for which you did not collect the minimum amount of carbon feed rate data required under §60.1335.
(2) Reasons you did not collect the minimum data.
(3) Corrective actions you took or are taking to get the required amount of data.
(d) Records of exclusions. Document each time you have excluded data from your calculation of average carbon feed rates and the reasons the data were excluded.
(e) Records of calendar dates. Include the calendar date on each record.