Most of Washington’s requirements for lockout/tagout (LOTO) are equivalent to the federal requirements; however, the state adds further requirements. A summary of the additional requirements includes the following:
- WAC 296-803-100 applies to the service and maintenance of piping systems, among other things.
- Gravity is an energy source, according to WAC 296-803-100.
- WAC 296-803 does not apply to, among other things, the service and maintenance of fire alarm and extinguishing systems and components if appropriate alternative measures protect those working on these systems from unexpected release of energy AND if other employees depend on these systems for fire safety.
- The energy control program called for at WAC 296-803-20005 must be in writing.
- Employers may write a single written energy control procedure for similar machines and equipment if the machines and equipment use the same energy type and magnitude, have the same or similar types of controls, and are identified in the procedure by specific machine/equipment type and location. See WAC 296-803-20005.
- According to WAC 296-803-40005, blank flanges and cribbing are two examples of means to control energy, among other examples.
- WAC 296-803-50040 differs from OSHA’s 29 CFR 1910.147(f)(1)(v) because the Washington state regulation is missing the step to deenergize all systems before reapplying the lockout or tagout devices when testing or positioning is completed.
- WAC 296-8003-50050 defines “primary authorized employee and says the primary authorized employee in group lockout/tagout is the last person to remove his/her lockout or tagout device when the job is completed.
- WAC 296-803-50055 says the employer must assign a primary authorized employee in each group, if more than one group will work on a machine or equipment that must be locked or tagged out.
- WAC 296-803-600 and WAC 296-803-700 use the term “periodic review” instead of the federal OSHA term “periodic inspection.”
- According to WAC 296-803-70005, an employer only needs to perform a review before using energy control procedures, if the procedures are used less than once a year.
- For energy control procedures involving only lockout devices, a group meeting will suffice in meeting the periodic review of authorized employees, according to WAC 296-803-70010. However, for energy control procedures involving tagout devices, periodic reviews of authorized and affected employees must be done individually.
- WAC 296-803-800 adds the following terms beyond OSHA’s 29 CFR
1910.147: “employer,” “primary authorized employee,” and “you.” WAC 296-
803-800 defines the following terms differently than 1910.147: “Can be locked
out” and “energy source.” - WAC 296-803 is missing a “Typical Minimal Lockout Procedure,” as found in OSHA’s 29 CFR 1910.147 Appendix A.
To ensure that you are in compliance with these requirements, click on the following links to view the state and federal regulations regarding LOTO:
Citations
Washington:
WAC 296-803 Lockout/Tagout (control of hazardous energy)
- WAC 296-803-100 Scope
- WAC 296-803-200 Summary
- WAC 296-803-20005 Establish a written energy control program
- WAC 296-803-300 Summary
- WAC 296-803-30005 Make sure new or modified machines and equipment can accept lockout devices
- WAC 296-803-400 Summary
- WAC 296-803-40005 Provide appropriate means to control energy
- WAC 296-803-40010 Make sure lockout and tagout devices meet these requirements
- WAC 296-803-40015 Make sure lockout devices meet these additional requirements
- WAC 296-803-40020 Make sure tagout devices meet these additional requirements
- WAC 296-803-500 Summary
- WAC 296-803-50005 Use energy control procedures
- WAC 296-803-50010 Meet these requirements when applying lockout or tagout devices
- WAC 296-803-50015 Meet these additional requirements when applying lockout devices
- WAC 296-803-50020 Meet these additional requirements when applying tagout devices
- WAC 296-803-50025 Protect employees from the hazards of stored and residual energy
- WAC 296-803-50030 Verify that the machine or equipment is safe before starting work
- WAC 296-803-50035 Meet these requirements when removing lockout or tagout devices and energizing the machine or equipment
- WAC 296-803-50040 Meet these requirements if it’s necessary to temporarily energize a machine, equipment, or component for testing or positioning
- WAC 296-803-50045 Protect employees during shift or personnel changes
- WAC 296-803-50050 Protect employees working in a group
- WAC 296-803-50055 Meet these additional requirements if more than one group is used
- WAC 296-803-50060 Coordinate with outside employers servicing or maintaining your machines or equipment
- WAC 296-803-600 Summary
- WAC 296-803-60005 Provide and document employee training on the energy control program
- WAC 296-803-60010 Provide additional training if you use tagout devices
- WAC 296-803-60015 Retrain employees when necessary
- WAC 296-803-700 Summary
- WAC 296-803-70005 Perform and document periodic reviews to verify employees know and follow the energy control procedures
- WAC 296-803-70010 Do periodic reviews of procedures using lockout devices
- WAC 296-803-70015 Do periodic reviews of procedures using tagout devices
- WAC 296-803-800 Definitions
Federal: 29 CFR 1910.147 and Appendix A
READ MORESHOW LESS
['Electrical Safety', 'Lockout/Tagout']
['Lockout/Tagout', 'Electrical Safety']
Load More
J. J. Keller is the trusted source for DOT / Transportation, OSHA / Workplace Safety, Human Resources, Construction Safety and Hazmat / Hazardous Materials regulation compliance products and services. J. J. Keller helps you increase safety awareness, reduce risk, follow best practices, improve safety training, and stay current with changing regulations.