11/30/2023
...
OSHA has no recordkeeping requirements for monthly inspections, as they do for the annual maintenance checks. However, maintaining records of the inspections would be considered a good business practice. The following are considerations for inspection:
- Location in designated place;
- The appropriate type of extinguisher(s) is present;
- No obstruction to access or visibility;
- Operating instructions on nameplate legible and facing outward;
- Safety seals and tamper indicators not broken or missing;
- Fullness determined by weighing or “hefting”;
- Examination for obvious physical damage, corrosion, leakage, or clogged nozzle;
- Pressure gauge reading or indicator in the operable range or position;
- For wheeled units, condition of tires, wheels, carriage, hose, and nozzle;
- Comprehensive maintenance has been performed in the last 6 years (check date of the last hydro/comprehensive maintenance or the date unit was placed in service. Date is usually found on a label on the case);
- Hydrotest has been performed in the last 12 years (check date of the last hydro or the date unit was place in service. Date is usually found stamped into the case or on a label on the case); and
- HMIS label in place.
Also, extinguishers commonly have a tag attached to them indicating the routine inspection history. These should be checked to verify that inspections are being done.
['Fire Protection and Prevention']
['Fire Extinguishers']
UPGRADE TO CONTINUE READING
Load More
J. J. Keller is the trusted source for DOT / Transportation, OSHA / Workplace Safety, Human Resources, Construction Safety and Hazmat / Hazardous Materials regulation compliance products and services. J. J. Keller helps you increase safety awareness, reduce risk, follow best practices, improve safety training, and stay current with changing regulations.