07/25/2021
...
[Editor’s Note: This section is removed and reserved effective January 1, 2022.]
(a)Precision.(1) For motor vehicle diesel fuel and diesel fuel additives subject to the 15 ppm sulfur standard of§80.520(a)(1)and NRLM diesel fuel and diesel fuel additives subject to the 15 ppm sulfur standard of§80.510(b)and (c), a standard deviation less than 0.72 ppm, computed from the results of a minimum of 20 tests made over 20 days (tests may be arranged into no fewer than five batches of four or fewer tests each, with only one such batch allowed per day over the minimum of 20 days) on samples taken from a single homogeneous commercially available diesel fuel with a sulfur content in the range of 5-15 ppm. The 20 results must be a series of tests with a sequential record of the analyses and no omissions. A laboratory facility may exclude a given sample or test result only if the exclusion is for a valid reason under good laboratory practices and it maintains records regarding the sample and test results and the reason for excluding them.
(2) For motor vehicle diesel fuel subject to the 500 ppm sulfur standard of §80.520(c), and for NRLM diesel fuel subject to the 500 ppm sulfur standard of §80.510(a), of a standard deviation less than 9.68 ppm, computed from the results of a minimum of 20 tests made over 20 days (tests may be arranged into no fewer than five batches of four or fewer tests each, with only one such batch allowed per day over the minimum of 20 days) on samples taken from a single homogeneous commercially available diesel fuel with a sulfur content in the range of 200-500 ppm. The 20 results must be a series of tests with a sequential record of the analyses and no omissions. A laboratory facility may exclude a given sample or test result only if the exclusion is for a valid reason under good laboratory practices and it maintains records regarding the sample and test results and the reason for excluding them.
(3) For ECA marine fuel subject to the 1,000 ppm sulfur standard of §80.510(k), of a standard deviation less than 18.07 ppm, computed from the results of a minimum of 20 tests made over 20 days (tests may be arranged into no fewer than five batches of four or fewer tests each, with only one such batch allowed per day over the minimum of 20 days) on samples taken from a single homogeneous commercially available diesel fuel with a sulfur content in the range of 700-1,000 ppm. The 20 results must be a series of tests with a sequential record of the analyses and no omissions. A laboratory facility may exclude a given sample or test result only if the exclusion is for a valid reason under good laboratory practices and it maintains records regarding the sample and test results and the reason for excluding them.
(b)Accuracy.(1) For motor vehicle diesel fuel and diesel fuel additives subject to the 15 ppm sulfur standard of§80.520(a)(1)and NRLM diesel fuel and diesel fuel additives subject to the 15 ppm sulfur standard of§80.510(b)and (c):
(i) The arithmetic average of a continuous series of at least 10 tests performed on a commercially available gravimetric sulfur standard in the range of 1-10 ppm sulfur shall not differ from the accepted reference value (ARV) of that standard by more than 0.54 ppm sulfur;
(ii) The arithmetic average of a continuous series of at least 10 tests performed on a commercially available gravimetric sulfur standard in the range of 10-20 ppm sulfur shall not differ from the ARV of that standard by more than 0.54 ppm sulfur; and
(iii) In applying the tests of paragraphs (b)(1)(i) and (ii) of this section, individual test results shall be compensated for any known chemical interferences.
(2) For motor vehicle diesel fuel subject to the 500 ppm sulfur standard of §80.520(c), and for NRLM diesel fuel subject to the 500 ppm sulfur standard of §80.510(a):
(i) The arithmetic average of a continuous series of at least 10 tests performed on a commercially available gravimetric sulfur standard in the range of 100-200 ppm sulfur shall not differ from the ARV of that standard by more than 7.26 ppm sulfur;
(ii) The arithmetic average of a continuous series of at least 10 tests performed on a commercially available gravimetric sulfur standard in the range of 400-500 ppm sulfur shall not differ from the ARV of that standard by more than 7.26 ppm sulfur; and
(iii) In applying the tests of paragraphs (b)(2)(i) and (ii) of this section, individual test results shall be compensated for any known chemical interferences.
(3) For ECA marine fuel subject to the 1,000 ppm sulfur standard of §80.510(k):
(i) The arithmetic average of a continuous series of at least 10 tests performed on a commercially available gravimetric sulfur standard in the range of 300-400 ppm sulfur shall not differ from the ARV of that standard by more than 13.55 ppm sulfur;
(ii) The arithmetic average of a continuous series of at least 10 tests performed on a commercially available gravimetric sulfur standard in the range of 900-1,000 ppm sulfur shall not differ from the ARV of that standard by more than 13.55 ppm sulfur; and
(iii) In applying the tests of paragraphs (b)(3)(i) and (ii) of this section, individual test results shall be compensated for any known chemical interferences.
[69 FR 39187, June 29, 2004, as amended at 75 FR 22971, Apr. 30, 2010; 80 FR 9096, Feb. 19, 2015; 85 FR 78467, Dec. 4, 2020]
READ MORESHOW LESS
Load More
J. J. Keller is the trusted source for DOT / Transportation, OSHA / Workplace Safety, Human Resources, Construction Safety and Hazmat / Hazardous Materials regulation compliance products and services. J. J. Keller helps you increase safety awareness, reduce risk, follow best practices, improve safety training, and stay current with changing regulations.