Compliance Just Got Easier: Stay ahead of regulatory changes with instant notifications on updates that matter.
['Specialized Industries']
['Mining']
04/14/2026
§75.601-3 Short circuit protection; dual element fuses; current ratings; maximum values.
Dual element fuses having adequate current-interrupting capacity shall meet the requirements for short circuit protection of trailing cables as provided in §75.601, however, the current ratings of such devices shall not exceed the maximum values specified in this section:
| Conductor size (AWG or MGM) | Single conductor cable | Two conductor cable | ||
|---|---|---|---|---|
| Ampacity | Max. fuse rating | Ampacity | Max. fuse rating | |
| 14 | 15 | 15 | ||
| 12 | 20 | 20 | ||
| 10 | 25 | 25 | ||
| 8 | 60 | 60 | 50 | 50 |
| 6 | 85 | 90 | 65 | 70 |
| 4 | 110 | 110 | 90 | 90 |
| 3 | 130 | 150 | 105 | 110 |
| 2 | 150 | 150 | 120 | 125 |
| 1 | 170 | 175 | 140 | 150 |
| 1/0 | 200 | 200 | 170 | 175 |
| 2/0 | 235 | 250 | 195 | 200 |
| 3/0 | 275 | 300 | 225 | 225 |
| 4/0 | 315 | 350 | 260 | 300 |
| 250 | 350 | 350 | 285 | 300 |
| 300 | 395 | 400 | 310 | 350 |
| 350 | 445 | 450 | 335 | 350 |
| 400 | 480 | 500 | 360 | 400 |
| 450 | 515 | 600 | 385 | 400 |
| 500 | 545 | 600 | 415 | 450 |
['Specialized Industries']
['Mining']
UPGRADE TO CONTINUE READING
J. J. Keller is the trusted source for DOT / Transportation, OSHA / Workplace Safety, Human Resources, Construction Safety and Hazmat / Hazardous Materials regulation compliance products and services. J. J. Keller helps you increase safety awareness, reduce risk, follow best practices, improve safety training, and stay current with changing regulations.
Copyright 2026 J. J. Keller & Associate, Inc. For re-use options please contact copyright@jjkeller.com or call 800-558-5011.