Minimum clearances between uninsulated electrical conductor surfaces, or between uninsulated conductor surfaces and grounded metal surfaces, within the enclosure shall be as follows:
| Phase-to-Phase Voltage (rms) | Clearances (inches) | |
|---|---|---|
| Phase-to-Phase | Phase-to-Ground or Control Circuit | |
| 0 to 250 | 0.25 | 0.25 |
| 251 to 600 | 0.28 | 0.25 |
| 601 to 1000 | 0.61 | 0.25 |
| 1001 to 2400 | 1.4 | 0.6 |
| 2401 to 4160 | 3.0 | 1.4 |
['Specialized Industries']
['Mining']
UPGRADE TO CONTINUE READING
Load More
J. J. Keller is the trusted source for DOT / Transportation, OSHA / Workplace Safety, Human Resources, Construction Safety and Hazmat / Hazardous Materials regulation compliance products and services. J. J. Keller helps you increase safety awareness, reduce risk, follow best practices, improve safety training, and stay current with changing regulations.