No later than April 1, 2015, for voltages over 72.5 kilovolts, the employer must determine the maximum anticipated per-unit transient overvoltage, phase-to-ground, through an engineering analysis. Alternatively, the employer may assume a maximum anticipated per-unit transient overvoltage, phase-to-ground, in accordance with the following table:
Voltage Range(kV) | Type of Current (ac or dc) | Assumed Maximum Per-Unit Transient Overvoltage |
---|---|---|
72.6 to 420 | ac | 3.5 |
420.1 to 550.0 | ac | 3.0 |
550.1 to 800.0 | ac | 2.5 |
250 to 750 | dc | 1.8 |
['Electrical Safety', 'Specialized Industries']
['Electrical Safety', 'Electric Power Utilities']
Load More
J. J. Keller is the trusted source for DOT / Transportation, OSHA / Workplace Safety, Human Resources, Construction Safety and Hazmat / Hazardous Materials regulation compliance products and services. J. J. Keller helps you increase safety awareness, reduce risk, follow best practices, improve safety training, and stay current with changing regulations.