['Water Programs']
['Point Sources', 'Toxic Water Pollutants', 'Industrial Wastewater', 'Total Maximum Daily Loads']
12/04/2024
...
Except as provided in §§125.30 through 125.32, and subject to the provisions of paragraph (a) of this section, any existing point source subject to this subpart shall achieve the following effluent limitations representing the degree of effluent reduction attainable by the application of the best practicable control technology currently available (BPT):
Effluent characteristic | Effluent limitations | |
---|---|---|
Maximum for any 1 day | Average of daily values for 30 consecutive days shall not exceed - | |
1 Within the range 6.0 to 9.0. | ||
Metric units (kg/Mwh) | ||
TSS | 0.319 | 0.160 |
Chromium total | .006 | .0032 |
Chromium VI | .0006 | .0003 |
Manganese total | .064 | .032 |
pH | (1) | (1) |
English units (lb/Mwh) | ||
TSS | .703 | .352 |
Chromium total | .014 | .007 |
Chromium VI | .0014 | .0007 |
Manganese total | .141 | .070 |
pH | (1) | (1) |
[39 FR 6809, Feb. 22, 1974, as amended at 60 FR 33957, June 29, 1995]
READ MORESHOW LESS
['Water Programs']
['Point Sources', 'Toxic Water Pollutants', 'Industrial Wastewater', 'Total Maximum Daily Loads']
Load More
J. J. Keller is the trusted source for DOT / Transportation, OSHA / Workplace Safety, Human Resources, Construction Safety and Hazmat / Hazardous Materials regulation compliance products and services. J. J. Keller helps you increase safety awareness, reduce risk, follow best practices, improve safety training, and stay current with changing regulations.